Fire resistant cables for evacuation systems - EVAC Series

Multicore unshielded

Cca Class – s1a, d0, a1 (CPR UE 305/2011)

Fixed applications, indoor

 

CONSTRUCTION
Inner conductor: Flexible bare copper wires
Insulation: Silicone-based elastomer blend (G29 quality)
Insulation color: (1) red, (2) black
Element assembly: Insulated cores stranded together with PET tape wrapping
Outer Jacket: FRNC-LSZH blend (M16 quality) – Purple RAL 4005

 

Article List

CEAM P/NCONSTRUCTIONNOM. EXT DIAMETER
[mm]
ELEM. STRAND.
[tors./m]
APPROX. WEIGHT
[kg/km]
MAX. PULLING FORCE
[N]
02088122x1,00mm27,1> 1262100 (ca. 10kg)
02088132x1,50mm27,7> 1178150 (ca. 15kg)
02088142x2,50mm28,8> 9112250 (ca. 25kg)

Properties

ELECTRICAL AND TRANSMISSION PROPERTIES

Max DC conductor resistance: 19,5Ω/km (1,00mm2) – 13,3Ω/km (1,50mm2) – 7,98Ω/km (2,50mm2)

Inductance: 0,64Ω/km (1,00mm2) – 0,70Ω/km (1,50mm2) – 0,70Ω/km (2,50mm2)

Attenuation (@1MHz): 1,40dB/100m (1,00mm2) – 1,30dB/100m (1,50mm2) – 1,20dB/100m (2,50mm2)

Insulation test voltage: 2,0 kVac x 15min

Jacket test voltage: 2,5 kVac x 5 min.

Characteristic impedance: 110 ± 10 Ω acc. with std. AES/EBU

Mutual capacitance: < 60 pF/m

Operating voltage (Uo/U): Max. 100/100V

OTHER PROPERTIES

Temperature rating: -30°C / +70°C

Min. bending radius: 10 x outer diam. [mm]

Standard reference: UNI 9795:2013; CEI 20-105:V2; EN 50200 (PH120); CEI EN 60332-3-25; CEI EN 60332-1-2; CEI EN 50267-2-1; CEI EN 50267-2-2; CEI EN 61034-2; CEI 20-11; CEI 20-29; CEI 20-52; CEI 46-76; EN 50575:2014+A1:2016; EN 50399; EN 13501-6; CEI UNEL 36762

Coexistance: allowed for cables belonging to cat. I systems, marked with 450/750V and 0,6/1kV (Uo = 400V)

Available lengths: 100m reel; 500/1000m drum