NETBUS L2/FIP P22M - Profibus™ DP Cable

S/FTP PUR 1x2x22/19AWG

Dynamic (drag chain) application, indoor/outdoor limited use

P/N: 0502453

 

CONSTRUCTION

Conductor: stranded bare copper wires – sez. 0,38mm² (22/19AWG)

Insulation: foam-skin polyethylene – diam. 2,8mm

Insulation colors: red; green

Core assembly: twisted to a pair with fillers (if needed)

Separation: non-woven PET/PA tape with overlap

Shielding:

  • AL/PET tape with overlap – AL surface outside
  • tinned copper wire braid – nom. coverage 85%

Outer jacket: PUR flame retardant and halogen free – Violet RAL 4001

Outer diam.: 8,1 (±0,2) mm

Properties

ELECTRICAL AND TRANSMISSION PROPERTIES

Max DC conductor resistance : 59,4 Ω/km

Capacitance (@800Hz): 30 nF/km (core/core)

Characteristic impedance: 150 Ω (±10%) @1÷20 MHz

Propagation velocity: 78%

Insulation resistance: ≥ 5,0 GΩxkm

Dielectric test voltage: 1,5 kVac /1 min (core/core); 1,5 kVac /1 min (core/shield)

Operating voltage: 300 V

 

FIRE PERFORMANCES

Flame retardant acc. with std. UL 1581 § 1060 (FT1), § 1061 (cable flame), § 1080 (VW-1) and IEC 60322-1-2

Determination of the amount of halogen acid gas acc. with std. EN 50267-2-1 e IEC 60754-1

Determination of degree of acidity of gases acc. with std. EN 50267-2-2 e IEC 60754-2

Heat release: 1259 MJ/km (0,349 kWh/m)

 

APPROVALS

UL/CSA: insulation acc. with AWM Style 10578 – 300V/80°C; jacket acc. with AWM Style 20233 – 300V/80°C

 

OTHER PROPERTIES

Temperature rating: -40°C / +80°C (fixed use); -30°C / +70°C (dynamic use)

Max. translation speed (axial drag chain): 3,0 m/s (subject to correct installation)

Max. acceleration (axial drag chain): 3,0 m/s² (subject to correct installation)

Max length (drag chain): 5m

Min. bending radius: 6 x Ø [mm] (fixed use); 12 x Ø [mm] (dynamic use)

Resistance to oils: acc. with std. IEC 60811-2-1; ASTM-oil 1; ICEA S-82-552

Resistance to UV: acc. with std. UL 1581 §1200

Resistance to muds: acc. with std. NEK 606

Resistance to ozone: acc. with std. VDE 0472 par.1

Resistance to microbes: acc. with std. VDE 0282/10

Good resistance to saturated hydrocarbons (diesel, kerosene, petrol ether)

Technical documents

Technical datasheet

Scroll to Top