Properties
ELECTRICAL AND TRANSMISSION PROPERTIES
Max DC conductor resistance: 72,2 Ω/km
Capacitance(@800Hz): 29 pF/km (core/core); 1500 pF/km (core/shield)
Characteristic impedance: 270 Ω (±10%) @9,6 kHz; 185 Ω (±10%) @38,4 kHz; 150 Ω (±10%) @1÷20 MHz
Propagation velocity: 76%
Insulation resistance: ≥ 5,0 GΩxkm
Dielectric test voltage: 2,0 kVac /1 min (core/core); 2,0 kVac /1 min (core/shield)
Operating voltage: 300 V
FIRE PERFORMANCES
Flame retardant acc. with std. UL 1581 § 1060 (FT1), § 1061 (cable flame) and IEC 60332-1
Determination of the amount of halogen acid gas acc. with std. EN 50267-2-1 e IEC 60754-1
Heat release: 1106 MJ/km (0,307 kWh/m)
APPROVALS
UL/CSA: insulation acc. with AWM Style 10578 – 300V/80°C; jacket acc. with AWM Style 20233 – 300V/80°C
Compliant to DESINA procedure.
OTHER PROPERTIES
Temperature rating: -40°C / +80°C (fixed use); -20°C / +60°C (dynamic use)
Max. translation speed (axial drag chain): 5,0 m/s (subject to correct installation)
Max. acceleration (axial drag chain): 5,0 m/s² (subject to correct installation)
Max length (drag chain): 5m
Min. bending radius: 7,5 x Ø [mm] (posa fissa); 12 x Ø [mm] (posa dinamica)
Max. pulling force: 100N
Standard reference: IEC 61158; EN 50170-2; DIN 19245; EIA RS485
Resistance to oils: acc. with std. IEC 60811-2-1; ASTM IRM 901; ICEA S-82-552
Resistance to mud: acc. with std. NEK 606
Resistance to ozone: acc. with std. VDE 0472 par.1
Resistance to microbes: acc. with std. VDE 0282/10
Good resistance to saturated hydrocarbons (diesel, kerosene, petrol ether)