NETBUS Z100 P125M - Cable for dynamic application

S/UTP PUR 1x2x0,25mm²

Dynamic (drag chain) application, indoor/outdoor limited use

P/N: 0502461

 

CONSTRUCTION

Conductor: stranded bare copper wires – sez. 0,25mm²

Insulation: solid polypropylene

Insulation colors: white; brown

Core assembly: twisted to a pair with fillers (if needed)

Separation: non-woven PET/PA tape with overlap

Shielding:

  • tinned copper wire braid – nom. coverage 85%

Separation: non-woven PET/PA tape with overlap

Outer jacket: PUR flame retardant and halogen free – Violet RAL 4001

Outer diam.: 4,7 (±0,2) mm

Properties

ELECTRICAL AND TRANSMISSION PROPERTIES

Max DC conductor resistance: 186,0 Ω/km

Capacitance (@800Hz): 60 nF/km

Characteristic impedance: 100÷120 Ω

Insulation resistance: ≥ 200 MΩxkm

Dielectric test voltage: 1,2 kVac /1 min (core/core); 0,75 kVac /1 min (core/shield)

Operating voltage: 250 V

 

FIRE PERFORMANCES

Flame retardant acc. with std. IEC 60332-1

Determination of the amount of halogen acid gas acc. with std. EN 50267-2-1 e IEC 60754-1

Determination of degree of acidity of gases acc. with std. EN 50267-2-2 e IEC 60754-2

 

OTHER PROPERTIES

Temperature rating: -40°C / +80°C (fixed use); -30°C / +70°C (dynamic use)

Max. translation speed (axial drag chain): 3,0 m/s (subject to correct installation)

Max. acceleration (axial drag chain): 3,0 m/s² (subject to correct installation)

Max length (drag chain): 5m

Min. bending radius: 5 x Ø [mm] (fixed use); 7,5 x Ø [mm] (dynamic use)

Standard reference: IEC 61158

Resistance to oils: acc. with std. IEC 60811-2-1; ASTM Oil 1; ICEA S-82-552

Resistance to UV: acc. with std. UL 1581 §1200

Resistance to muds: acc. with std. NEK 606

Resistance to ozone: acc. with std. EN 50396

Resistance to microbes: acc. with std. VDE 0282/10